Properties

Improved conventional grain-oriented (CGO) electrical steels are supplied in the fully processed state and have properties exceeding the requirements of the conventional grades described in EN 10107:2014. As well as the maximum loss and minimum polarisation levels cited, full magnetic characterisation curves regarding losses, polarisation, permeability and apparent power at different frequencies are available on request.

Advantages

Improved CGO electrical steels provide lower losses and higher polarisation levels than conventional CGO grades. The improved CGO grades have a magnetic polarisation at 800 A/m of minimum 1.85 T, which is higher than the EN 10107:2014 requirement of 1.75 or 1.78 T. This means it is possible to use these grades at a higher working point than conventional grades, and in different applications, such as transformers and self-induction coils. With a higher working point, the transformer can be made smaller, which enables cost-savings in terms of the quantity of magnetic and conductor materials needed. Obviously, a higher working point can lead to higher losses, making the transformer less efficient, which is why ArcelorMittal offers its improved CGO grades only with low losses, so this effect is taken into account.

Applications

Improved CGO grades can be used in any application where conventional CGO grades are used, but can be advantageous where there is a need, for instance, to reduce the no-load losses of a transformer. These improved grades should be regarded as a product category between conventional (C) GO and high-permeability (H) GO. HGO has the advantage of further reducing losses and increasing polarisation, albeit at increased product cost. Improved CGO grades find their market in applications requiring improved performance in a cost-efficient way.

Recommendations for use

The above properties are measured according to EN 10107 using either Epstein measuring equipment or a Single Sheet Tester (SST). This standard specifies the need for stress-relief annealing, after cutting the samples, depending on the measuring device.

Brand correspondence

 
Thickness 0.23 mm
 JIS C 2553:2012
M 105-23 S AM FCE * 
Grades in italics: not included in the standard
* After prior agreement
 
Thickness 0.27 mm
 JIS C 2553:2012
M 114-27 S AM FCE  
Grades in italics: not included in the standard
 
Thickness 0.30 mm
 JIS C 2553:2012
M 117-30 S AM FCE 30P120
Grades in italics: not included in the standard
 
Thickness 0.35 mm
 JIS C 2553:2012
M 125-35 S AM FCE  
Grades in italics: not included in the standard

Dimensions

        
Thickness 0.23 mm 
 NotesSide trimmedSlit coilsSheet length 700 to 3000 mm
Min widthMax widthMin widthMax widthMin widthMax width
M 105-23 S AM FCE 60097040600600970
        
Thickness 0.27 mm 
 NotesSide trimmedSlit coilsSheet length 700 to 3000 mm
Min widthMax widthMin widthMax widthMin widthMax width
M 114-27 S AM FCE 60097040600600970
        
Thickness 0.30 mm 
 NotesSide trimmedSlit coilsSheet length 700 to 3000 mm
Min widthMax widthMin widthMax widthMin widthMax width
M 117-30 S AM FCE160097040600600970
        
Thickness 0.35 mm 
 NotesSide trimmedSlit coilsSheet length 700 to 3000 mm
Min widthMax widthMin widthMax widthMin widthMax width
M 125-35 S AM FCE160097040600600970
1. Larger width available after prior agreement
Grades in italics: not included in the standard

 

Magnetic properties


 
Thickness 0.23 mm
 
Conventional density (kg/dm≥)
Max loss (W/kg) at 50 Hz at 1.5 T
Max loss (W/kg) at 50 Hz at 1.7 T
Max loss (W/kg) at 60 Hz at 1.7 T
Min polarisation (T) at 800 A/m
Min number of bends
Min stacking factor (mm)
 IndicativeGuaranteedIndicativeGuaranteedGuaranteedGuaranteed
M 105-23 S AM FCE 7.65 0.73 1.05 1.38 1.85 1 0.945
Grades in italics: not included in the standard
Multiply the values in W/kg by 0.4536 to obtain the values in W/lb.
 
Thickness 0.27 mm
 
Conventional density (kg/dm≥)
Max loss (W/kg) at 50 Hz at 1.5 T
Max loss (W/kg) at 50 Hz at 1.7 T
Max loss (W/kg) at 60 Hz at 1.7 T
Min polarisation (T) at 800 A/m
Min number of bends
Min stacking factor (mm)
 IndicativeGuaranteedIndicativeGuaranteedGuaranteedGuaranteed
M 114-27 S AM FCE 7.65 0.78 1.14 1.50 1.85 1 0.950
Grades in italics: not included in the standard
Multiply the values in W/kg by 0.4536 to obtain the values in W/lb.
 
Thickness 0.30 mm
 
Conventional density (kg/dm≥)
Max loss (W/kg) at 50 Hz at 1.5 T
Max loss (W/kg) at 50 Hz at 1.7 T
Max loss (W/kg) at 60 Hz at 1.7 T
Min polarisation (T) at 800 A/m
Min number of bends
Min stacking factor (mm)
 IndicativeGuaranteedIndicativeGuaranteedGuaranteedGuaranteed
M 117-30 S AM FCE 7.65 0.81 1.17 1.55 1.85 1 0.955
Grades in italics: not included in the standard
Multiply the values in W/kg by 0.4536 to obtain the values in W/lb.
 
Thickness 0.35 mm
 
Conventional density (kg/dm≥)
Max loss (W/kg) at 50 Hz at 1.5 T
Max loss (W/kg) at 50 Hz at 1.7 T
Max loss (W/kg) at 60 Hz at 1.7 T
Min polarisation (T) at 800 A/m
Min number of bends
Min stacking factor (mm)
 IndicativeGuaranteedIndicativeGuaranteedGuaranteedGuaranteed
M 125-35 S AM FCE 7.65 0.92 1.25 1.65 1.85 1 0.960
Grades in italics: not included in the standard
Multiply the values in W/kg by 0.4536 to obtain the values in W/lb.


Coating properties

These grades are available with the coating described in data sheet D60.


 


For commercial information (quotations, deliveries, product availability):

For technical questions about these products: flateurope.technical.assistance@arcelormittal.com